Cerabar M
22 Endress+Hauser
Vibrations effects Within the reference accuracy vor vibration amplitudes below:
0 ... 15 Hz: 4 mm (amplitude of distance)
15 ... 150 Hz: 2 g (amplitude of acceleration)
150 ... 2000 Hz: 1g (amplitude of acceleratrion)
Warm-up period 4 to 20 mA: 200 ms
4 to 20 mA HART: 1 s
PROFIBUS PA: 1 s
Rise time (T90) 4 to 20 mA: 60 ms
4 to 20 mA HART: 220 ms
PROFIBUS PA: 220 ms
Settling time 4 to 20 mA: 180 ms
4 to 20 mA HART: 600 ms
PROFIBUS PA: 600 ms
P01-xxxxxxxx-05-xx-xx-xx-025
Case 3, example 3 and 4
Sensor measuring range
Extended measuring range
Pressure applied at the device, see Case 3, Example 3
Pressure applied at the device, see Case 3, Example 4
LRL Lower-range limit
URL Upper-range limit
Case 3:
•4 to 20 mA
Example 3:
Sensor measuring range: 0 to 10 bar
Extended measuring range: –0.5 to 10.5 bar
A pressure of 0.5 bar is applied at the device. The zero
point can be adjusted in the range –0.5 to 1.5 bar.
Example 4:
Sensor measuring range: 0 to 10 bar
Extended measuring range: -0.5 to 10.5 bar
A pressure of 1 bar is applied at the device. The zero point
can be adjusted in the range 0 to 2 bar.
LRL
URL
5 % URL
5 % URL
±10
% URL
±10
% URL