Cerabar M
Endress+Hauser 9
Human interface
Onsite display (optional) Analog display for devices with analog electronics
A plug-in liquid crystal display (LCD), with a bar graph for showing the current (30 segments), is used as the
display unit. The display can be rotated in 90° stages.
Functions:
• Bar graph to indicate the measured value from 0 to 100%. This corresponds to a signal current of 4 to 20 mA.
• The scale flashes to indicate signal undershoot (current < 3.8 mA).
• The bar graph and scale flash to indicate signal overshoot (current > 20.5 mA).
P01-PMx4xxxx-07-xx-xx-xx-000
Onsite display for devices with analog electronics
➀ Bar graph
➁ Scale
➂ Cell measuring range
Digital display for devices with 4 to 20 mA HART or PROFIBUS PA electronics
A plug-in digital display, with a 4-digit pressure display and bar graph (28 segments), is used as the display unit.
The display can be rotated in 90° stages.
Functions:
• 4-digit pressure display
• Bar graph
– 4 to 20 mA HART: the bar graph displays the current value (4 to 20 mA) belonging to the pressure value.
– PROFIBUS PA: the bar graph displays the current pressure value in relation to the set measuring range.
• Easy diagnosis by displaying an error code
P01-PMx4xxxx-07-xx-xx-xx-001
Onsite display for devices with 4 to 20 mA HART or PROFIBUS PA electronics
A Display in measuring mode
B Display in calibration mode
➀ 4-digit display of measured values and input parameters
➁ Bar graph, display of current measured value
➂ Lower-range value
➃ Upper-range value
➄ Set measuring range in measuring limits
➅ Display of calibration point (Z (Zero) = lower-range value (LRV) or S (Span) = upper-range value (URV))
➆ Nominal measuring range
0%
50%
100%
0…1 bar
➀
➁
➂
0…1 bar
0.753
0.753
0.250
Z
S
A:
B:
➀
➂
➁
➃