Cerabar M
12 Endress+Hauser
Input
Measured variable Absolute pressure or overpressure
Measuring range PMC41 and PMC45 with ceramic measuring diaphragm (Ceraphire
®
) for overpressure
PMC41 and PMC45 with ceramic measuring diaphragm (Ceraphire
®
) for negative overpressure
PMC41 and PMC45 with ceramic measuring diaphragm (Ceraphire
®
) for absolute pressure
Nominal value Measurement limits Smallest span
that can be
calibrated
OPL
1
MWP
2
Vacuum
resistance
Version in the
order code
3
lower (LRL) upper (URL)
[bar] [bar] [bar] [bar] [bar] [bar
abs
]
100 mbar 0 0.1 0.01 4 2.7 0.7 1C
400 mbar 0 0.4 0.04 8 5.3 0 1F
1 bar 0 1 0.1 10 6.7 0 1H
4 bar 0 4 0.4 25 16.7 0 1M
10 bar 0 10 1 40 26.7 0 1P
40 bar 0 40 4 60 40 0 1S
Nominal value Measurement limits Smallest span
that can be
calibrated
OPL
1
MWP
2
Vacuum
resistance
Version in the
order code
3
lower (LRL) upper (URL)
[bar] [bar] [bar] [bar] [bar] [bar
abs
]
100 mbar –0.1 0.1 0.02 4 2.7 0.7 5C
400 mbar –0.4 0.4 0.08 8 5.3 0 5F
1 bar –1 1 0.2 10 6.7 0 5H
4 bar –1 4 0.5 25 16.7 0 5M
10 bar –1 10 1.1 40 26.7 0 5P
Nominal value Measurement limits Smallest span
that can be
calibrated
OPL
1
MWP
2
Vacuum
resistance
Version in the
order code
3
lower (LRL) upper (URL)
[bar
abs
][bar
abs
][bar] [bar
abs
][bar
abs
][bar
abs
]
400 mbar 0 0.4 0.04 8 5.3 0 2F
1 bar 0 1 0.1 10 6.7 0 2H
4 bar 0 4 0.4 25 16.7 0 2M
10 bar 0 10 1 40 26.7 0 2P
40 bar 0 40 4 60 40 0 2S
1) OPL: overpressure limit
2) The MWP (maximum working pressure) for the measuring device depends on the element of the selected components which has the lowest pressure
rating, i.e. the process connection (
→ see Page 31 ff) has to be taken into consideration in addition to the measuring cell (→ see Table above). Please also
observe the pressure-temperature dependencies. For the appropriate standards and further information, see Page 30, "Pressure specifications" section.
3) Version in the order code → see also Page 67 ff, feature 30 "Sensor range; MWP, OPL"