Deltabar FMD71, FMD72 Installation
Endress+Hauser 23
5.10 Seal for flange mounting
NOTICE
Distorted measurement results.
The seal is not allowed to press against the process isolating diaphragm as this could affect
the measurement result.
Ensure that the seal is not touching the process isolating diaphragm.
1 2
A0017743
1 Process isolating diaphragm
2 Seal
5.11 Post-installation check
Is the device undamaged (visual inspection)?
Does the device comply with the measuring point specifications?
For example:
Process temperature
Process pressure
Ambient temperature
Measuring range
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected against precipitation and direct sunlight?
Are the securing screw and securing clamp tightened securely?