Operation options Deltabar FMD71, FMD72
36 Endress+Hauser
Accepting the pressure present
Example: setting position adjustment.
Menu path: Main menu → Setup → Pos. zero adjust
Pos. zero adjust 007 Software operation
1 Cancel The pressure for position adjustment is present at the device.
Confirm
2 Cancel Use or to switch to the "Confirm" option. The active option is highlighted
in black.
Confirm
3 Adjustment has
been accepted!
Use the key to accept the applied pressure as a position adjustment. The
device confirms the adjustment and goes back to the "Pos. zero adjust"
parameter.
4 Cancel Use to exit edit mode for the parameter.
Confirm
User-definable parameters
Example: setting parameter "Set URV (014)" from 100 mbar (1.5 psi) to 50 mbar (0.75
psi).
Menu path: Setup → Extended setup → Current output → Set URV
Set URV 014 Software operation
The onsite display shows the parameter to be changed. The "mbar" unit
is defined in another parameter and cannot be changed here.
1
1 0 0 . 0 0 0
mbar
Press or to get to edit mode. The first digit is highlighted in
black.
2
1 0 0 . 0 0 0
mbar
Use the key to change "1" to "5". Press the key to confirm "5".
Cursor jumps to the next position. Use the key to confirm (second
position).
3
5 0 0 . 0 0 0
mbar
The third digit is highlighted in black and can now be edited.
4
5 0 0 . 0 0 0
mbar
Use the key to change to the " " symbol. Use to save the new
value and exit edit mode. See next graphic.
5
5 0
¿
. 0 0 0
mbar
The new value for the full scale value is 50.0 mbar (0.75 psi). Use to
exit edit mode for the parameter. Use or to return to edit mode.
6
5 0 . 0 0 0
mbar
7.6 Operation using Endress+Hauser operating program
The FieldCare operating program is an Endress+Hauser asset management tool based on
FDT technology. With FieldCare, you can configure all Endress+Hauser devices as well as
devices from other manufacturers that support the FDT standard.
Hardware and software requirements can be found on the Internet:
www.de.endress.com → Search: FieldCare → FieldCare → Technical data.