Commissioning Deltabar FMD71, FMD72
58 Endress+Hauser
9.11 Linearization
9.11.1 Manual entry of a linearization table
Example:
In this example, the volume in a tank with a conical outlet should be measured in m
3
.
Prerequisite:
This is a theoretical calibration, i.e. the points for the linearization table are known.
The "Level" measuring mode has been selected.
A level calibration has been performed.
The linearization characteristic must rise or fall continuously.
For a description of the parameters mentioned, →  78"Description of parameters".
L
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked in
the "Setup" operating menu and readjusted if necessary.
Description
1 Select the "Manual entry" option via the "Lin.
mode (037)" parameter.
Menu path: Setup → Extended setup →
Linearization → Lin. mode
v
h
A0017669
h Height
v Volume
2 Select using the "Unit after lin. (038)"
parameter, e.g. m
3
.
Menu path: Setup → Extended setup →
Linearization → Unit after lin.