Integrating transmitter via HART
®
protocol
Deltabar FMD71, FMD72
40 Endress+Hauser
8
Integrating transmitter via HART
®
protocol
Version data for the device
Firmware version 01.00.zz • On the title page of the Operating instructions
• On the nameplate → 15
• Firmware Version parameter
Diagnosis → Instrument info→ Firmware Version
Manufacturer ID 17 (0x11) Manufacturer Id parameter
Diagnosis → Instrument info → Manufacturer ID
Device type code 39 (0x27) Device type code parameter
Diagnosis → Instrument info → Device type code
HART protocol revision 6.0 ---
Device revision 1 • On the transmitter nameplate → 15
• Device revision parameter
Diagnosis → Instrument info → Device revision
The suitable device description file (DD) for the individual operating tools is listed in the
table below, along with information on where the file can be acquired.
Operating tools
Operating tool Reference sources for device descriptions (DD and DTM)
FieldCare • www.endress.com → Download-Area
• CD-ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
AMS Device Manager
(Emerson Process Management)
www.endress.com → Download-Area
SIMATIC PDM
(Siemens)
www.endress.com → Download-Area
Field Communicator 375, 475
(Emerson Process Management)
Use update function of handheld terminal
8.1 HART process variables and measured values
The following numbers are assigned to the process variables in the factory:
Process variable Pressure Level
Linear Table active
First process variable
(Primary Variable (PV))
0
(Measured
differential pressure)
8
(Level before
linearization)
9
(Tank content)
Second process variable
(Secondary Variable (SV))
2
(Measured
pressure HP)
0
(Measured
differential pressure)
8
(Level before
linearization)