Deltabar FMD71, FMD72 Description of Device Parameters
Endress+Hauser 91
14.6 Setup → Extended Setup → Linearization
Lin. mode (037)
Navigation Setup → Extended setup → Linearization → Lin. mode (037)
Write permission Operators/Service engineers/Expert
Description Select the linearization mode.
Options • Linear
The level is output without being converted beforehand. "Level before lin" is output.
• Erase table
The existing linearization table is deleted.
• Manual entry (sets the table to edit mode, an alarm is output):
The value pairs of the table (X-value (193/040) and Y-value (041)) are entered
manually.
• Semi-automatic entry (sets the table to edit mode, an alarm is output):
The vessel is emptied or filled in stages in this entry mode. The device automatically
records the level value (X-value (193/040)). The associated volume, mass or % value is
entered manually (Y-value (041)).
• Activate table
The table entered is activated and checked with this option. The device shows the level
after linearization.
Factory setting Linear
Unit after lin. (038)
Navigation Setup → Extended Setup → Linearization → Unit after lin. (038)
Write permission Operators/Service engineers/Expert
Description Select volume unit, mass, height or % (unit of the Y-value).
Options • %
• cm, dm, m, mm
• hl
• in
3
, ft
3
, m
3
,
• l
• in, ft
• kg, t
• lb
• gal
• Igal
Factory setting %