Deltabar FMD71, FMD72 Description of Device Parameters
Endress+Hauser 91
14.6 Setup → Extended Setup → Linearization
Lin. mode (037)
Navigation Setup → Extended setup → Linearization → Lin. mode (037)
Write permission Operators/Service engineers/Expert
Description Select the linearization mode.
Options Linear
The level is output without being converted beforehand. "Level before lin" is output.
Erase table
The existing linearization table is deleted.
Manual entry (sets the table to edit mode, an alarm is output):
The value pairs of the table (X-value (193/040) and Y-value (041)) are entered
manually.
Semi-automatic entry (sets the table to edit mode, an alarm is output):
The vessel is emptied or filled in stages in this entry mode. The device automatically
records the level value (X-value (193/040)). The associated volume, mass or % value is
entered manually (Y-value (041)).
Activate table
The table entered is activated and checked with this option. The device shows the level
after linearization.
Factory setting Linear
Unit after lin. (038)
Navigation Setup → Extended Setup → Linearization → Unit after lin. (038)
Write permission Operators/Service engineers/Expert
Description Select volume unit, mass, height or % (unit of the Y-value).
Options %
cm, dm, m, mm
hl
in
3
, ft
3
, m
3
,
l
in, ft
kg, t
lb
gal
Igal
Factory setting %