Deltabar FMD71, FMD72 Diagnostics and troubleshooting
Endress+Hauser 69
Diagnostic event Cause Corrective measure
Code Description
S841 Sensor range Overpressure or low pressure present.
Sensor module defective.
Check the pressure value
Contact Endress+Hauser
Service
S945 Pressure limit LP The configured overpressure or underpressure
limit of the sensor module LP is exceeded.
Sensor module LP defective.
Check the pressure value
Change pressure limit value
Contact Endress+Hauser
Service
S971 Adjustment The current is outside the permitted range 3.8 to
20.5 mA.
The present pressure value is outside the
configured measuring range (but within the
sensor module range, if applicable).
Check the pressure value
Check the measuring range
Check the setting
10.3 Response of output to errors
The response of the current output to errors is defined in the following parameters:
"Alarm behav. P (050)" →  93
"Output fail mode (190)" →  94
"High alarm curr. (052)" →  94