Deltabar FMD71, FMD72 Commissioning
Endress+Hauser 43
L
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
If the measuring mode is changed, the setting for the span (URV) must be checked and
readjusted if necessary.
Perform position adjustment (see information at the start of "Commissioning" section.)
1 Device is installed. Process pressure is not present.
2  Press key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 Applied pressure for position adjustment has been
accepted.
Applied pressure for position adjustment has not been
accepted. Observe the input limits.
Setting lower range value.
1 Desired pressure for lower range value is present at device.
2  Press key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 Applied pressure for lower range value has been
accepted.
Applied pressure for lower range value has not been
accepted. Observe the input limits.
Setting upper range value.
1 Desired pressure for upper range value is present at device.
2  Press key for at least 3 s.
3 Does the LED on the electronic insert light up briefly?
4 Yes No
5 Applied pressure for upper range value has been
accepted.
Applied pressure for upper range value has not been
accepted. Observe the input limits.
9.3.2 Level measuring mode
If no local display is connected, the following functions are possible via the three keys on
the electronic insert or externally on the device: