Deltabar FMD71, FMD72 Description of Device Parameters
Endress+Hauser 81
High press. side (183)
Navigation Setup → High press. side (183)
Write permission Operators/Service engineers/Expert
Description Define which sensor module corresponds to the high-pressure side.
Options • Sensor HP
• Sensor LP
Factory setting Sensor HP
Press. eng. unit (125)
Navigation Setup → Press. eng. unit (125)
Write permission Operators/Service engineers/Expert
Description Select the pressure engineering unit. If a new pressure engineering unit is selected, all
pressure-specific parameters are converted and displayed with the new unit.
Options • mbar, bar
• mmH2O, mH2O
• in, H2O, ftH2O
• Pa, kPa, MPa
• psi
• mmHg, inHg
• kgf/cm
2
Factory setting mbar, bar or psi depending on the sensor module nominal measuring range, or as per
order specifications
Corrected press. (172)
Navigation
Setup → Corrected press. (172)
Diagnosis → Measured values → Corrected press. (172)
Write permission No write permissions. Parameter is read only.6
Description Displays the measured differential pressure after position adjustment.
Pos. zero adjust (007)