Deltapilot S
16 Endress+Hauser
Supply voltage Note!
When using the measuring device in hazardous areas, installation must comply with the corresponding
national standards and regulations and the Safety Instructions (XAs) or Installation or Control Drawings
(ZDs).
All explosion protection data are given in separate documentation which is available upon request. The Ex
documentation is supplied as standard with all devices approved for use in explosion hazardous areas. See
also Page 59 ff, "Safety Instructions" and "Installation/Control Drawings" sections.
0.2 to 1.2 mA analog
15 to 20 V DC
PFM
Version for non-hazardous areas: 14 to 16 V DC
4 to 20 mA HART
Version for non-hazardous areas: 11.5 to 30 V DC
PROFIBUS PA
Version for non-hazardous areas and electronics without overvoltage protection: 9 to 32 V DC
Version for non-hazardous areas and electronics with overvoltage protection: 9.6 to 32 V DC
FOUNDATION Fieldbus
Version for non-hazardous areas: 9 to 32 V DC
Current consumption PROFIBUS PA
10 mA ± 1 mA
FOUNDATION Fieldbus
11 mA ± 1 mA
Switch-on current 0.1 to 1.2 mA analog, PFM and 4 to 20 mA HART
100 mA for 30 V, pulse width half-life 20 ms
PROFIBUS PA and FOUNDATION Fieldbus
Switch-on current corresponds to Table 4, IEC 611158-2, Clause 2
Cable entry See also Page 37 ff, feature 80 "Housing; Cable entry".
Cable specification 0.1 to 1.2 mA analog
Endress+Hauser recommends using a shielded, three-core instrument cable with max. 25 Ω per core.
Terminals for wire cross-section: 0.08 to 2.5 mm
2
PFM
Endress+Hauser recommends using a shielded, twin-core instrument cable with max. 25 Ω per core.
Terminals for wire cross-section: 0.08 to 2.5 mm
2
4 to 20 mA HART, PROFIBUS PA and FOUNDATION Fieldbus
Endress+Hauser recommends using a twisted, shielded twin-core cable.
Terminals for wire cross-section: 0.08 to 2.5 mm
2