Appendix Ecograph T, RSG35
104 Endress+Hauser
Comparison point
Navigation Expert → Inputs → Universal inputs → Universal input x → Comparison point
Direct access code: 220013-0xx
Examples: Universal input 1: 220013-000; Universal input 12: 220013-011
Description Internal: Compensation of the voltage error by measuring the terminal temperature.
External: Compensation of the voltage error by using an external controlled comparison
measurement point.
Only visible if signal = thermocouple.
Options Internal, External
Factory setting Internal
Comparison temp.
Navigation Expert → Inputs → Universal inputs → Universal input x → Comparison temp.
Direct access code: 220014-0xx
Examples: Universal input 1: 220014-000; Universal input 12: 220014-011
Description Settings for the external comparison temperature (only when connecting thermocouples).
Only visible if comparison point = external.
User entry 0 to 9999999 (Depends on the temperature unit selected)
Factory setting 0 (Depends on the temperature unit selected)
Totalizer
Navigation Expert → Inputs → Universal inputs → Universal input x → Totalizer
Direct access code: 220015-0xx
Examples: Universal input 1: 220015-000; Universal input 12: 220015-011
Description Initial setting for the totalizer. Useful when continuing measurements recorded to date
with an (electro)-mechanical counter.
Only visible if signal = pulse counter
User entry Number (max. 15 digits)
Factory setting 0