Appendix Ecograph T, RSG35
108 Endress+Hauser
Unit
Navigation Expert → Inputs → Universal inputs → Universal input x → Totalization → Unit
Direct access code: 220032-0xx
Examples: Universal input 1: 220032-000; Universal input 12: 220032-011
Description Enter the unit for the calculated quantity (e.g. "m³").
Only visible if totalization = yes.
User entry Text (max. 6 characters)
Low flow cut off
Navigation Expert → Inputs → Universal inputs → Universal input x → Totalization → Low flow
cut off
Direct access code: 220033-0xx
Examples: Universal input 1: 220033-000; Universal input 12: 220033-011
Description If the volume flow recorded is below the set value, these quantities are not added to the
counter.
If the input is scaled from 0 to y, or if the pulse input is used, all values that are smaller
than the set value are not recorded.
If the input is scaled from -x to +y, all values around the zero point (e.g. also negative
values) are not recorded.
Only visible if totalization = yes.
User entry Number (max. 8 digits)
Factory setting 0
Calc. factor
Navigation Expert → Inputs → Universal inputs → Universal input x → Totalization → Calc.
factor
Direct access code: 220034-0xx
Examples: Universal input 1: 220034-000; Universal input 12: 220034-011
Description Factor for calculating the integrated value (e.g. the transmitter delivers l/s -> totalization
base = second -> engineering unit required is m³ -> enter factor 0.001)
Only visible if totalization = yes.
User entry Number (max. 8 digits)
Factory setting 1.0