Ecograph T, RSG35 Appendix
Endress+Hauser 109
Totalizer
Navigation Expert → Inputs → Universal inputs → Universal input x → Totalization → Totalizer
Direct access code: 220035-0xx
Examples: Universal input 1: 220035-000; Universal input 12: 220035-011
Description Initial setting for the totalizer. Useful when continuing measurements recorded to date
with an (electro)-mechanical counter.
Only visible if totalization = yes.
User entry Number (max. 15 digits)
Factory setting 0
"Fault mode" submenu
In the event of an error the alarm relay is switched if so configured →  79
Navigation Expert → Inputs → Universal inputs → Universal input x → Fault mode
Description Contains settings that define how this channel is to react under fault conditions (e.g. cable
open circuit, over range).
NAMUR NE 43
Navigation Expert → Inputs → Universal inputs → Universal input x → Fault mode → NAMUR
NE 43
Direct access code: 220060-0xx
Examples: Universal input 1: 220060-000; Universal input 12: 220060-011
Description Activate/deactivate the 4-20mA loop monitoring as per NAMUR recommendation NE 43.
The following error ranges apply when NAMUR NE43 is switched on:
≤ 3.8 mA: under range
≥ 20.5 mA: over range
≤ 3.6 mA or ≥ 21.0 mA: sensor error
≤ 2 mA: cable open circuit
Only visible if signal = "Current" and range = "4-20 mA" or "4-20 mA squared".
Options Off, On
Factory setting On
Cable open circ.