EasyManua.ls Logo

Endress+Hauser Ecograph RSG35 - Page 110

Endress+Hauser Ecograph RSG35
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix Ecograph T, RSG35
110 Endress+Hauser
Navigation Expert → Inputs → Universal inputs → Universal input x → Fault mode → Cable open
circ.
Direct access code: 220060-0xx
Examples: Universal input 1: 220060-000; Universal input 12: 220060-011
Description Cable open circuit detection
Only visible if signal = "Voltage" and range = "1-5 V" or "1-5 V squared".
Options Off, On
Factory setting On
Lower error value
Navigation Expert → Inputs → Universal inputs → Universal input x → Fault mode → Lower error
value
Direct access code: 220065-0xx
Examples: Universal input 1: 220065-000; Universal input 12: 220065-011
Description When NE43 is switched off, defines the value that must be undershot for the device to
output an error.
Only visible if signal = "Current", range = "4-20 mA", and NAMUR NE 43 = "Off".
User entry Number (max. 8 digits); 0 to 4 mA
Factory setting 3.9mA
Upper error value
Navigation Expert → Inputs → Universal inputs → Universal input x → Fault mode → Upper error
value
Direct access code: 220066-0xx
Examples: Universal input 1: 220066-000; Universal input 12: 220066-011
Description When NE43 is switched off, defines the value that must be exceeded for the device to
output an error.
Only visible if signal = "Current", range = "4-20 mA", and NAMUR NE 43 = "Off".
User entry Number (max. 8 digits); 20 to 22mA
Factory setting 20.8mA
Time delay

Table of Contents