Ecograph T, RSG35 Appendix
Endress+Hauser 111
Navigation Expert → Inputs → Universal inputs → Universal input x → Fault mode → Time delay
Direct access code: 220064-0xx
Examples: Universal input 1: 220064-000; Universal input 12: 220064-011
Description The device only reacts (e.g. Relay switch) when this condition, open circuit/under range/
over range, has been operational for the preset time.
Only visible if NAMUR NE 43 = on.
User entry 0 to 99 s
Factory setting 0s
On error
Navigation Expert → Inputs → Universal inputs → Universal input x → Fault mode → On error
Direct access code: 220061-0xx
Examples: Universal input 1: 220061-000; Universal input 12: 220061-011
Description Configure what value the device should continue working with (for calculations) if the
measured value is not valid (e.g. cable open circuit).
In the event of an error value, all the dependent calculations are flagged accordingly
as "error value". Counters are not flagged, however!
Options Invalid calculation, Error value
Factory setting Invalid calculation
Error value
Navigation Expert → Inputs → Universal inputs → Universal input x → Fault mode → Error value
Direct access code: 220062-0xx
Examples: Universal input 1: 220062-000; Universal input 12: 220062-011
Description The device continues calculating with this value in the event of an error.
Only visible if On error = Error value.
User entry Number (max. 8 digits)
Factory setting 0
Save event
Navigation Expert → Inputs → Universal inputs → Universal input x → Fault mode → Save event
Direct access code: 220063-0xx
Examples: Universal input 1: 220063-000; Universal input 12: 220063-011