Ecograph T, RSG35 Appendix
Endress+Hauser 115
Navigation Expert → Inputs → Digital inputs → Digital input x → Pulse value
Direct access code: 250005-00x
Examples: Digital input 1: 250005-000; Digital input 6: 250005-005
Description Factor, that when multiplied by the input signal results in the required physical value.
Examples:
1 pulse equals 5 m
3
-> enter "5".
Only visible if function = pulse counter.
User entry Number (max. 8 digits)
Factory setting 1
1 second=/1 hour= (depends on the setting in "Input factor in")
Navigation Expert → Inputs → Digital inputs → Digital input x → 1 second=/1 hour=
Direct access code: 250005-00x
Examples: Digital input 1: 250005-000; Digital input 6: 250005-005
Description Factor, that when multiplied by the operating time results in the required physical value.
Examples:
1 second equals 8 l -> enter "8".
Only visible if function = quantity from time.
User entry Number (max. 8 digits)
Factory setting 1
Time delay
Navigation Expert → Inputs → Digital inputs → Digital input x → Time delay
Direct access code: 250017-00x
Examples: Digital input 1: 250017-000; Digital input 6: 250017-005
Description The high signal must be active for at least the preset time before the device changes the
channel from low to high.
The change from high to low is always immediate.
Only visible if function = control input, on/off event, event+operation time.
User entry 0 to 99 999 s
Factory setting 0
Action