Ecograph T, RSG35 Appendix
Endress+Hauser 155
Description Enter a name for these groups.
User entry Text (max. 20 characters)
Factory setting Group x
Save cycle
Navigation Expert → Application → Signal groups → Group x → Save cycle
Direct access code: 460001-0xx
Examples: Group 1: 460001-000; Group 4: 460001-003
Description Configure the save cycle with which this group should be saved in normal conditions (see
also set point/save cycle).
The save cycle is independent of the measured value display (see Operating
Instructions).
Options Off, 1s, 2s, 3s, 4s, 5s, 10s, 15s, 20s, 30s, 1min, 2min, 3min, 4min, 5min, 10min, 15min,
30min, 1h
Factory setting 1min
Alarm cycle
Navigation Expert → Application → Signal groups → Group x → Alarm cycle
Direct access code: 460002-0xx
Examples: Group 1: 460002-000; Group 4: 460002-003
Description Configure the save cycle with which this group should be saved in an alarm condition (set
point violation).
Attention: Requires higher memory capacity.
Options Off, 1s, 2s, 3s, 4s, 5s, 10s, 15s, 20s, 30s, 1min, 2min, 3min, 4min, 5min, 10min, 15min,
30min, 1h
Factory setting 1min
Display blue
Navigation Expert → Application → Signal groups → Group x → Display blue
Direct access code: 460003-00x
Examples: Group 1: 460003-000; Group 4: 460003-003
Description Choose which input/calculate variable should be displayed in this group.
Options Switched off, Universal input x, Digital input x, Maths x