iTEMP TMT82 Technical data
Endress+Hauser 53
Description Standard
Ambient temperature:
Influence (±) per 1 °C (1.8 °F) change
Supply voltage:
Influence (±) per V change
Type L (43)
GOST
R8.8585-2001
≤ 0.01 °C
(0.02 °F)
-
≤ 0.01 °C
(0.02 °F)
-
Voltage transmitter (mV)
0.001 % 0.001 %
–20 to
100 mV
- ≤ 3 µV - ≤ 3 µV -
1)
Measured value transmitted via HART
®
.
2) Percentages based on the configured span of the analog output signal
MV = Measured Value
LRV = Lower Range Value of relevant sensor
Total measured error of transmitter at current output = √(Measured error digital² +
Measured error D/A²)
Long-term drift, resistance thermometers (RTD) and resistance transmitters
Description Standard Long-term drift (±)
after 1 year after 3 years after 5 years
Based on measured value
Pt100 (1)
IEC 60751:2008
≤ 0.03 °C (0.05 °F) + 0.024% x
span
≤ 0.042 °C (0.076 °F) + 0.035% x
span
≤ 0.051 °C (0.092 °F) + 0.037% x
span
Pt200 (2)
≤ 0.17 °C (0.31 °F) + 0.016% x
span
≤ 0.28 °C (0.5 °F) + 0.022% x span
≤ 0.343 °C (0.617 °F) + 0.025% x
span
Pt500 (3)
≤ 0.067 °C (0.121 °F) + 0.018% x
span
≤ 0.111 °C (0.2 °F) + 0.025% x
span
≤ 0.137 °C (0.246 °F) + 0.028% x
span
Pt1000 (4)
≤ 0.034 °C (0.06 °F) + 0.02% x
span
≤ 0.056 °C (0.1 °F) + 0.029% x
span
≤ 0.069 °C (0.124 °F) + 0.032% x
span
Pt100 (5) JIS C1604:1984
≤ 0.03 °C (0.054 °F) + 0.022% x
span
≤ 0.042 °C (0.076 °F) + 0.032% x
span
≤ 0.051 °C (0.092 °F) + 0.034% x
span
Pt50 (8)
GOST 6651-94
≤ 0.055 °C (0.1 °F) + 0.023% x
span
≤ 0.089 °C (0.16 °F) + 0.032% x
span
≤ 0.1 °C (0.18 °F) + 0.035% x span
Pt100 (9)
≤ 0.03 °C (0.054 °F) + 0.024% x
span
≤ 0.042 °C (0.076 °F) + 0.034% x
span
≤ 0.051 °C (0.092 °F) + 0.037% x
span
Ni100 (6)
DIN 43760 IPTS-68
≤ 0.025 °C (0.045 °F) + 0.016% x
span
≤ 0.042 °C (0.076 °F) + 0.02% x
span
≤ 0.047 °C (0.085 °F) + 0.021% x
span
Ni120 (7)
≤ 0.021 °C (0.038 °F) + 0.018% x
span
≤ 0.032 °C (0.058 °F) + 0.024% x
span
≤ 0.036 °C (0.065 °F) + 0.025% x
span
Cu50 (10)
OIML R84: 2003 /
GOST 6651-2009
≤ 0.053 °C (0.095 °F) + 0.013% x
span
≤ 0.084 °C (0.151 °F) + 0.016% x
span
≤ 0.094 °C (0.169 °F) + 0.016% x
span
Cu100 (11)
≤ 0.027 °C (0.049 °F) + 0.019% x
span
≤ 0.042 °C (0.076 °F) + 0.026% x
span
≤ 0.047 °C (0.085 °F) + 0.027% x
span
Ni100 (12)
≤ 0.026 °C (0.047 °F) + 0.015% x
span
≤ 0.04 °C (0.076 °F) + 0.02% x
span
≤ 0.046 °C (0.083 °F) + 0.02% x
span
Ni120 (13)
≤ 0.021 °C (0.038 °F) + 0.017% x
span
≤ 0.034 °C (0.061 °F) + 0.022% x
span
≤ 0.038 °C (0.068 °F) + 0.023% x
span
Cu50 (14)
OIML R84: 2003 /
GOST 6651-94
≤ 0.056 °C (0.1 °F) + 0.009% x
span
≤ 0.089 °C (0.16 °F) + 0.011% x
span
≤ 0.1 °C (0.18 °F) + 0.011% x span
Resistance transmitter
10 to 400 Ω ≤ 10mΩ + 0.022% x span ≤ 14mΩ + 0.031% x span ≤ 16mΩ + 0.033% x span
10 to 2 000 Ω ≤ 144mΩ + 0.019% x span ≤ 238mΩ + 0.026% x span ≤ 294mΩ + 0.028% x span