Operating menu and parameter description iTEMP TMT82
72 Endress+Hauser
Navigation Setup → Advanced setup → Locking status
Expert → Locking status
Description Use this function to view the device locking status. The DIP switch for hardware locking is
fitted on the display module. When write protection is activated, write access to the
parameters is disabled. → 26
Device temperature alarm
Navigation Setup → Advanced setup → Device temperature alarm
Description Use this function to select the category (status signal) as to how the device reacts when
the electronics temperature of the transmitter exceeds or falls below the limit value < -40
°C (-40 °F) or > +85 °C (+185 °F).
Options • Off
• Out of specification (S)
• Failure (F)
Factory setting Out of specification (S)
"Sensor" submenu
Sensor offset n
n = Stands for the number of sensor inputs (1 and 2)
Navigation Setup → Advanced setup → Sensor → Sensor offset n
Expert → Sensor → Sensor n → Sensor offset n
Description Use this function to set the zero point correction (offset) of the sensor measured value.
The value indicated is added to the measured value.
User entry -10.0...+10.0
Factory setting 0.0
Corrosion detection
Navigation Setup → Advanced setup → Sensor → Corrosion detection
Expert → Sensor → Diagnostic settings → Corrosion detection