iTEMP TMT82 Operating menu and parameter description
Endress+Hauser 97
Prerequisite The Customer-specific option is enabled in the Sensor trimming parameter→ 96 .
Description Lower point for linear characteristic calibration (this affects offset and slope).
User entry Depends on the selected sensor type and the assignment of the current output (PV).
Factory setting -200 °C
Sensor trimming upper value
Navigation Expert → Sensor → Sensor n → Sensor trimming → Sensor trimming upper value
Prerequisite The Customer-specific option is enabled in the Sensor trimming parameter.
Description Upper point for linear characteristic calibration (this affects offset and slope).
User entry Depends on the selected sensor type and the assignment of the current output (PV).
Factory setting 850 °C
Sensor trimming min span
Navigation Expert → Sensor → Sensor n → Sensor trimming → Sensor trimming min span
Prerequisite The Customer-specific option is enabled in the Sensor trimming parameter.
Description Use this function to view the minimum possible span between the sensor trimming upper
and lower value.
"Linearization" submenu
Procedure for configuring a linearization using Callendar/Van Dusen coefficients from a
calibration certificate.
1. Start
ß
2. Assign current output (PV) = set sensor 1 (measured value)
ß
3. Select unit (°C).
ß
4. Select the sensor type (linearization type) "RTD platinum (Callendar/Van Dusen)".
ß
5. Select connection mode e.g. 3-wire.
ß
6. Set the lower and upper sensor limits.
ß