Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Commissioning via operating menu
Endress+Hauser 101
9. Navigate to: Setup → Empty calibration
Enter the distance E between the reference point R and the minimum level (0%).
10. Navigate to: Setup → Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.
11. Navigate to: Setup → Level
Displays the measured level L
L
.
12. Navigate to: Setup → Interface
Displays the interface height L
I
.
13. Navigate to: Setup → Distance
Displays the distance D
L
between the reference point R and the level L
L
.
14. Navigate to: Setup → Interface distance
Displays the distance D
I
between the reference point R and the interface L
I
.
15. Navigate to: Setup → Signal quality
Displays the signal quality of the level echo.
16. For operation via local display:
Navigate to: Setup → Mapping → Confirm distance
Compare the displayed distance to the real distance in order to start the
recording of the mapping curve if required
4)
.
17. For operation via operating tool (e.g. FieldCare):
Navigate to: Setup → Confirm distance
Angezeigte Distanz mit tatsächlichem Wert vergleichen, um gegebenenfalls die
Aufnahme einer Störechoausblendungskurve zu starten
4)
.
4) For FMP54 with gas phase compensation (product structure: feature 540 "Application Package", option EF or EG) a map must NOT be recorded.