Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus Operating menu
Endress+Hauser 171
Mapping end point
Navigation Setup → Map. end point
Prerequisite Confirm distance (→ 169) = Manual map or Distance too small
Description Specify new end of the mapping.
User entry 0 to 200 000.0 m
Factory setting 0.1 m
Additional information This parameter defines up to which distance the new mapping is to be recorded. The
distance is measured from the reference point, i.e. from the lower edge of the mounting
flange or the threaded connection.
For reference purposes the Present mapping parameter (→ 170) is displayed
together with this parameter. It indicates up to which distance a mapping has already
been recorded.
Record map
Navigation Setup → Record map
Prerequisite Confirm distance (→ 169) = Manual map or Distance too small
Description Start recording of the map.
Selection • No
• Record map
• Delete map
Factory setting No
Additional information Meaning of the options
• No
The map is not recorded.
• Record map
The map is recorded. After the recording is completed, the new measured distance and
the new mapping range appear on the display. When operating via the local display,
these values must be confirmed by pressing .
• Delete map
The mapping (if one exists) is deleted and the device displays the recalculated measured
distance and the mapping range. When operating via the local display, these values must
be confirmed by pressing .