Operating menu Levelflex FMP55 HART
118 Endress+Hauser
Interface distance
Navigation  Setup → Interface dist.
Prerequisite Operating mode (→  111) = Interface or Interface with capacitance
Description Displays the measured distance D
I
between the reference point (lower edge of flange or
threaded connection) and the interface.
Additional information
D
I
D
I
A0013202
The unit is defined in the Distance unit parameter (→  111).
Confirm distance
Navigation Setup → Confirm distance
Description Specify, whether the measured distance matches the real distance.
Depending on the selection the device automatically sets the range of mapping.
Selection Manual map
Distance ok
Distance unknown
Distance too small
*
Distance too big
*
Tank empty
Delete map
Factory setting Distance unknown