Operating menu Levelflex FMP55 HART
154 Endress+Hauser
"Switch output" submenu
Navigation  Setup → Advanced setup → Switch output
Switch output function
Navigation  Setup → Advanced setup → Switch output → Switch out funct
Description Select function for switch output.
Selection Off
On
Diagnostic behavior
Limit
Digital Output
Factory setting Off
Additional information Meaning of the options
Off
The output is always open (non-conductive).
On
The output is always closed (conductive).
Diagnostic behavior
The output is normally closed and is only opened if a diagnostic event is present. The
Assign diagnostic behavior parameter (→  155) determines for which type of event
the output is opened.
Limit
The output is normally closed and is only opened if a measured variable exceeds or falls
below a defined limit. The limit values are defined by the following parameters:
Assign limit (→  155)
Switch-on value (→  156)
Switch-off value (→  157)
Digital Output
The switching state of the output tracks the output value of a DI function block. The
function block is selected in the Assign status parameter (→  154).
The Off and On options can be used to simulate the switch output.
Assign status
Navigation  Setup → Advanced setup → Switch output → Assign status
Prerequisite Switch output function (→  154) = Digital Output
Description Select device status for switch output.
Selection Off
Digital output AD 1
Digital output AD 2