Levelflex FMP55 HART Operating menu
Endress+Hauser 151
Process variable 4 mA value 20 mA value
Thickness upper layer 0 %
1)
or the associated
linearized value
100 %
2)
or the associated linearized value
Relative interface amplitude 0 mV 2 000 mV
1) the 0% level is defined by Empty calibration parameter (→  113)
2) The 100% level is defined by Full calibration parameter (→  114)
It may be necessary to adjust the 4mA and 20mA values to the application (especially
in the case of the Analog output adv. diagnostics 1/2 option ).
This can be done by the following parameters:
Expert → Output → Curr.output 1 to 2 → Turn down
Expert → Output → Curr.output 1 to 2 → 4 mA value
Expert → Output → Curr.output 1 to 2 → 20 mA value
Current span
Navigation  Setup → Advanced setup → Curr.output 1 to 2 → Current span
Description Select current range for process variable and alarm signal.
Selection 4...20 mA
4...20 mA NAMUR
4...20 mA US
Fixed current
Factory setting 4...20 mA NAMUR
Additional information Meaning of the options
Option Current range for process
variable
Lower alarm signal level Upper alarm signal level
4...20 mA 4 to 20.5 mA < 3.6 mA > 21.95 mA
4...20 mA NAMUR 3.8 to 20.5 mA < 3.6 mA > 21.95 mA
4...20 mA US 3.9 to 20.8 mA < 3.6 mA > 21.95 mA
Fixed current Constant current, defined in the Fixed current parameter (→  152).
In the case of an error, the output current assumes the value defined in the Failure
mode parameter (→  152).
If the meausred value is out of the measuring range, diagnostic message Current
output is issued.
In a HART multidrop loop only one device can use the analog current to transmit a
signal. For all other devices one must set:
Current span = Fixed current
Fixed current (→  152) = 4 mA