Levelflex FMP55 HART Operating menu
Endress+Hauser 153
Additional information Meaning of the options
• Min.
The current output adopts the value of the lower alarm level according to the Current
span parameter (→ 151).
• Max.
The current output adopts the value of the upper alarm level according to the Current
span parameter (→ 151).
• Last valid value
The current remains constant at the last value it hat before the error occurred.
• Actual value
The output current follows the actual measured value; the error is ignored.
• Defined value
The output current assumes the value defined in the Failure current parameter
(→ 153).
The error behavior of other output channels is not influenced by these settings but is
defined in separate parameters.
Failure current
Navigation Setup → Advanced setup → Curr.output 1 to 2 → Failure current
Prerequisite Failure mode (→ 152) = Defined value
Description Enter current output value in alarm condition.
User entry 3.59 to 22.5 mA
Factory setting 22.5 mA
Output current 1 to 2
Navigation Setup → Advanced setup → Curr.output 1 to 2 → Output curr. 1 to 2
Description Displays calculated output current.