Operating menu Levelflex FMP55 HART
188 Endress+Hauser
Current output 1 to 2 simulation
Navigation Expert → Diagnostics → Simulation → Curr.out. 1 to 2 sim.
Description Switch the simulation of the current output on or off.
Selection • Off
• On
Factory setting Off
Additional information An active simulation is indicated by a diagnostic message of the Function check (C)
category.
Value current output 1 to 2
Navigation Expert → Diagnostics → Simulation → Value curr.out 1 to 2
Prerequisite Current output simulation (→ 188) = On
Description Enter current value for the simulation
User entry 3.59 to 22.5 mA
Factory setting 3.59 mA
Additional information The current output assumes the value specified in this parameter. In this way, users can
verify the correct adjustment of the current output and the correct function of connected
control units.
Switch output simulation
Navigation Expert → Diagnostics → Simulation → Switch sim.
Description Switch the simulation of the switch output on or off.
Selection • Off
• On
Factory setting Off