Levelflex FMP55 HART Operating menu
Endress+Hauser 189
Switch status
Navigation Expert → Diagnostics → Simulation → Switch status
Prerequisite Switch output simulation (→ 188) = On
Description Define the switch state to be simulated.
Selection • Open
• Closed
Factory setting Open
Additional information The switch status assumes the value defined in this parameter. This helps to check correct
operation of connected control units.
Device alarm simulation
Navigation Expert → Diagnostics → Simulation → Dev. alarm sim.
Description Switch alarm simulation on or off.
Selection • Off
• On
Factory setting Off
Additional information When selecting the On option, the device generates an alarm. This helps to check the
correct output behavior of the device in the case of an alarm.
An active simulation is indicated by the diagnostic message C484 Failure mode
simulation.
Diagnostic event simulation
Navigation Expert → Diagnostics → Simulation → Diag. event sim.
Prerequisite Access status display (→ 123)/Access status tooling (→ 122) = Service
Description Select diagnostic event to be simulated.
Factory setting Off
Additional information When operated via the local display, the selection list can be filtered according to the event
categories (Diagnostic event category parameter).