Operating menu Levelflex FMP55 HART
150 Endress+Hauser
"Current output 1 to 2" submenu
The Current output 2 submenu (→ 150) is only available for devices with two
current outputs.
Navigation Setup → Advanced setup → Curr.output 1 to 2
Assign current output 1 to 2
Navigation Setup → Advanced setup → Curr.output 1 to 2 → Assign curr.
Description Select process variable for current output.
Selection • Level linearized
• Distance
• Electronic temperature
• For FMP55: Measured capacitance
• Relative echo amplitude
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Additionally for Operating mode = "Interface" or "Interface with capacitance":
• Interface linearized
• Interface distance
• Thickness upper layer
• Relative interface amplitude
Factory setting For interface measurements
• Current output 1: Interface linearized
• Current output 2
9)
: Level linearized
Additional information Definition of the current range for the process variables
Process variable 4 mA value 20 mA value
Level linearized 0 %
1)
or the associated
linearized value
100 %
2)
or the associated linearized value
Distance 0 (i.e. level is at the reference
point)
Empty calibration (→ 113) (i.e. level is at
0 %)
Electronic temperature –50 °C (–58 °F) 100 °C (212 °F)
Measured capacitance 0 pF 4 000 pF
Relative echo amplitude 0 mV 2 000 mV
Analog output adv.
diagnostics 1/2
depending on the parametrization of the Advanced Diagnostics
Interface linearized 0 %
1)
or the associated
linearized value
100 %
2)
or the associated linearized value
Interface distance 0 (i.e. interface at the
reference point)
Empty calibration (→ 113) (i.e. interface
is at 0 %)
9) only for devices with two current outputs