Endress+Hauser Liquiline CM44 series - FC03 Read Holding Register; FC04 Read Input Register

Endress+Hauser Liquiline CM44 series
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SD01189C/07/EN/04.17
Endress+Hauser
10 © Copyright Dec. 2016
3.4.1 FC03 Read Holding Register
Request
Function code
1 Byte
0x03
Starting address
2 Byte
0x0000 to 0xFFFF
Quantity of Registers
2 Byte
1 to 125 (0x7D)
Response
Function code
1 Byte
0x03
Byte Count
1 Byte
2 * Quantity of Registers
Holding register value
(2 * Quantity of Registers) Byte
2 to 250
Error
Error code
1 Byte
0x83
Exception code
1 Byte
01 or 02 or 03 or 04
3.4.2 FC04 Read Input Register
Request
Function code
1 Byte
0x04
Starting address
2 Byte
0x0000 to 0xFFFF
Quantity of Registers
2 Byte
1 to 125 (0x7D)
Reply
Function code
1 Byte
0x04
Byte Count
1 Byte
2 * Quantity of Registers
Holding register value
(2 * Quantity of Registers) Byte
2 to 250
Error
Error code
1 Byte
0x84
Exception code
1 Byte
01 or 02 or 03 or 04