SD01189C/07/EN/04.17
Endress+Hauser
47
8.3.5 Sensors
The X in the paramter list is a variable that describes the sensor number. See also the other Sensors
respectively registers in the table below.
Sensor
Register
X =
Sensor 1
1000-1999
1
Sensor 2
2000-2999
2
Sensor 3
3000-3999
3
Sensor 4
4000-4999
4
Sensor 5
5000-5999
5
Sensor 6
6000-6999
6
Sensor 7
7000-7999
7
Sensor 8
8000-8999
8
8.3.5.1 Sensor X (Input, FC: 04)
Register
Data Type
Bytes
R/W
Unit
Description
X000
UNSIGNED8
1
R
None
Activation of sensor channel
Selection:
0: On (default)
1: Off
X001
UNSIGNED8
1
R
None
Selected sensor type. The selected type has to match with the connected
sensor type.
Selection:
0: None (default)
1: Oxygen (amp.)
2: Oxygen (opt. fixed cable)
3: pH Glass
4: pH/ORP
5: pH ISFET
6: Cond c
7: Cond i
8: ORP
9: TU/TS
10: Nitrate
11: ISE
12: SAC
13: Ultrasonic interface
14: Chlorine
18: pH/ORP
19: Cond c 4-pol
20: Oxygen (opt. Memosens coupling)
21: TU
22: Inline photometer
X002
UNSIGNED8
1
R
None
Connected sensor type
Selection:
0: None (default)
1: Oxygen (amp.)
2: Oxygen (opt. fixed cable)
3: pH Glass
5: pH ISFET
6: Cond c
7: Cond i
8: ORP
9: TU/TS
10: Nitrate
11: ISE
12: SAC
13: Ultrasonic interface
14: Chlorine
18: pH/ORP
19: Cond c 4-pol

Table of Contents