SD01189C/07/EN/04.17
Endress+Hauser
23
The status signal can be read via the Modbus diagnostic function code #08 or directly as a parameter.
Sensor 1 has a diagnostic message
Sensor 2 has a diagnostic message
Sensor 3 has a diagnostic message
Sensor 4 has a diagnostic message
Sensor 5 has a diagnostic message
Sensor 6 has a diagnostic message
Sensor 7 has a diagnostic message
Sensor 8 has a diagnostic message
General diagnostic message
Status signal F (failure)
Status signal C (function check)
Status signal M (maintenance required)
Status signal S (out of specification)
The FCMS error category can be adapted individually for each diagnostic message.
For device related diagnostic messages:
Path: Menu/Setup/General settings/Extended setup/Diagnostics settings/Diag. behavior
For sensor related diagnostic messages:
Path: Menu/Setup/Inputs/<Sensor>/Extended setup/Diagnostics settings/Diag. behavior
5.4 Diagnostic messages
Via Modbus registers, the device provides detailed information on the current diagnostic message with the
highest priority and the last diagnostic message to be displayed. This information is available for the
device and for each sensor.
The diagnostic codes and the corrective measures which can be taken based on the error code, are
described in the Operating Instructions "Maintenance & diagnostics".
5.4.1 Device related diagnostics
Current, active diagnostic message with the highest priority:
DEVICE_CURRENT_DIAG_MODUL
Slot number 0 to 7 of the
module.
Connection 0 to 3 on the module.
DEVICE_CURRENT_DIAG_NE107_STATUS
Bit 0: Failure (F)
Bit 1: Function check (C)
Bit 2: Maintenance (M)
Bit 3: Out of specification (S)
Bit 4-7: Reserved = 0
Diagnostic code (0 to 999)
DEVICE_CURRENT_DIAG_TIMESTAMP
Time stamp (seconds since
1.1.1970)