8 Modbus tables
8.1 Numbering of Modbus-Registers
The numbering of the Modbus registers starts with 0 as it is transmitted over the wire. In case your PLC
is using Modicon addressing you have to add 1 to the addresses as provided in the following tables.
8.2 Factory default values
If not otherwise specified in the tables the default value of a parameter is 0.
8.3 General
8.3.1 Identification (Input, FC: 04)
Register
Data Type
Bytes
R/W
Unit
Description
9000
UNSIGNED8
1
R
None
Modbus connection setting : bus address
Factory default: 247
9001
OCTETSTRING32
32
R
None
Device description / TAG
9017
UNSIGNED8
1
R
None
Device ID
Selection:
0: Liquiline CM442 (default)
1: Liquiline CM448
2: Liquiport CSP44
3: Liquistation CSF48
4: Liquistation CSF22
5: Liquistation CSF33
6: Liquiline System CA80
7: Liquistation CSF34
8: Liquistation CSF39
9: Liquiline CM44P
8.3.2 Process (Holding/Input, FC: 03, 16, 23, 04)
The connection of the device variables AI1-16, DI1-8, AO1-4 and DO1-8 to the actual process values is
described in chapter 4.5.
Register
Data Type
Bytes
R/W
Unit
Description
0
FLOAT
4
R
None
AI1: Analog process value from device to control system : value
2
UNSIGNED8
1
R
None
AI1: Analog process value from device to control system : state
3
UNSIGNED8
1
R
None
AI1: Analog process value from device to control system : unit
4
FLOAT
4
R
None
AI2: Analog process value from device to control system : value
6
UNSIGNED8
1
R
None
AI2: Analog process value from device to control system : state
7
UNSIGNED8
1
R
None
AI2: Analog process value from device to control system : unit
8
FLOAT
4
R
None
AI3: Analog process value from device to control system : value
10
UNSIGNED8
1
R
None
AI3: Analog process value from device to control system : state
11
UNSIGNED8
1
R
None
AI3: Analog process value from device to control system : unit
12
FLOAT
4
R
None
AI4: Analog process value from device to control system : value
14
UNSIGNED8
1
R
None
AI4: Analog process value from device to control system : state
15
UNSIGNED8
1
R
None
AI4: Analog process value from device to control system : unit
16
FLOAT
4
R
None
AI5: Analog process value from device to control system : value
18
UNSIGNED8
1
R
None
AI5: Analog process value from device to control system : state
19
UNSIGNED8
1
R
None
AI5: Analog process value from device to control system : unit
20
FLOAT
4
R
None
AI6: Analog process value from device to control system : value
22
UNSIGNED8
1
R
None
AI6: Analog process value from device to control system : state
23
UNSIGNED8
1
R
None
AI6: Analog process value from device to control system : unit
24
FLOAT
4
R
None
AI7: Analog process value from device to control system : value
26
UNSIGNED8
1
R
None
AI7: Analog process value from device to control system : state