4 Commissioning
4.1 Modbus RS485
The parameters are located in Setup/General settings/Extended setup/Modbus/Settings.
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Even (1 Stopbit), Odd (1 Stopbit), None (1 Stoppbit), None
(2 Stoppbit)
1-0-3-2, 1-0-2-3, 2-3-0-1, 3-2-1-0
0 … 999, 0 = Watchdog is deactivated.
If the device does not receive a valid MODBUS request
telegram, a diagnostic code S969 (Modbus Watchdog) and
the red BF LED are set. The next valid Modbus request will
remove this diagnose.
The setting of the bus address with the Address-Switch of the module has priority over the menu setting. If
a valid address is set, the bus address in the menu is read only.
Valid bus addresses are between 1 and 247. If you configure an invalid address, software addressing is
automatically enabled via the onsite setting.