Register
Data Type
Bytes
R/W
Unit
Description
Selection:
0: Auto negotiation (default)
1: 10MBps Half duplex
2: 10MBps Full duplex
3: 100MBps Half duplex
4: 100MBps Full duplex
517
UNSIGNED8
1
R/W
None
Command for controlling ethernet statistics
Selection:
0: No operation (default)
1: Retransmitt error counters
2: Reset error counters
518
UNSIGNED8
1
R/W
None
Dynamic setting of device IP address (DHCP)
Selection:
0: Off
1: On (default)
519
UNSIGNED8
1
R/W
None
Webserver activation
Selection:
0: Off
1: On (default)
520
UNSIGNED16
2
R/W
None
Device reset
521
UNSIGNED8
1
R/W
None
Setting of byte transmission sequence
Selection:
0: 1-0-3-2 (default)
1: 0-1-2-3
2: 2-3-0-1
3: 3-2-1-0
600
OCTETSTRING32
32
R/W
None
Device description / TAG
Factory default: E_TextID_DeviceTAGDefault
700
FLOAT
4
R/W
None
Controller : set value for controller 0
702
FLOAT
4
R/W
None
Controller : proportional band (Xp) for controller 0
Factory default: 10.0
704
FLOAT
4
R/W
Seconds
Controller : reset time (Tn) for controller 0
706
FLOAT
4
R/W
Seconds
Controller : rate time (Tv) for controller 0
708
FLOAT
4
R/W
None
Controller : set value for controller 1
710
FLOAT
4
R/W
None
Controller : proportional band (Xp) for controller 1
Factory default: 10.0
712
FLOAT
4
R/W
Seconds
Controller : reset time (Tn) for controller 1
714
FLOAT
4
R/W
Seconds
Controller : rate time (Tv) for controller 1
716
DATETIME
8
R/W
None
Real-Time Clock
Factory default: 2009-01-01T12:00:00