Liquistation CSF48 Technical data
Endress+Hauser 255
15.8.5 EtherNet/IP
15.8.6 Web server
The web server enables full access to the device configuration, measured values, diagnostic
messages, logbooks and service data via standard WiFi/WLAN/LAN/GSM or 3G router with a
user-defined IP address.
Protocol EtherNet/IP
ODVA certification Yes
Device profile Generic device (product type: 0x2B)
Manufacturer ID 0x049E
h
Device type ID 0x109C
h
Polarity Auto-MIDI-X
Connections (max.) CIP 12
I/O 6
Explicit message 6
Multicast 3 consumers
Minimum RPI 100 ms (default)
Maximum RPI 10000 ms
System integration EtherNet/IP EDS
Rockwell Add-on-Profile Level 3, Faceplate for FactoryTalk SE
IO data Input (T --> O) Device status and top-priority diagnostic message
Measured values:
16 AI (analog input) + status + unit
8 DI (discrete input) + status
Output (O --> T) Actuating values:
4 A0 (analog output) + status + unit
8 DO (discrete output) + status
TCP port 80
Supported features Remote-controlled device configuration (1 session)
Device configuration saved/restored
Logbook export (file formats: CSV, FDM)
Web server accessed via DTM or Internet Explorer
•Login
Web server can be switched off