What to do if I can't change parameters on my Endress+Hauser Measuring Instruments?
- Kkevin40Aug 2, 2025
If you cannot change parameters, consider these points: 1. Some parameters are read-only and cannot be changed. 2. The hardware write protection may be enabled. Disable write protection. You can check the write protection status via the WRITE_LOCK parameter in the Resource Block. 3. The block operating mode might be incorrect. Change parameters in OOS or MAN mode via the MODE_BLK parameter group. 4. The value entered may be outside the allowed range. Enter a suitable value or increase the input range if possible. 5. For Transducer Blocks, the programming level might not be enabled. Enable it by entering the code in the "Un-/Locking - Access Code" parameter or using the Service Code.