11 Operation via FOUNDATION Fieldbus Proline Prowirl 72 FOUNDATION Fieldbus
108 Endress + Hauser
Un-/Locking -
Define Private
Code
AUTO - OOS Use this function to specify the personal code used to enable the
configuration of the manufacturer-specific parameters in the Transducer
Blocks.
User input:
Max. 4-digit number: 0 to 9999
Factory setting:
72
! Note!
• Programming is always enabled if the code defined = 0.
• Programming has to be enabled before this code can be changed. When
programming is disabled this function cannot be edited, thus preventing
others from accessing your personal code.
Line 1-
Assign
AUTO - OOS Use this function to define which display value is assigned to the main line
(top line of the local display) for display during normal measuring operation.
Options:
Off
Volume Flow
Volume Flow in %
Mass Flow
Mass Flow in %
Corr. Volume Flow
Corr. Volflow in %
Totalizer 1
AI1 - OUT VALUE
AI2 - OUT VALUE
Factory setting:
Volume Flow
Line 1 -
100%-Value
AUTO - OOS
! Note!
The entry made only becomes effective if one of the following options was
selected in the "Line 1 - Assign" parameter:
Volume Flow in %
Mass Flow in %
Corr. Volflow in %
Use this function to specify the flow value to be shown on the display as the
100% value.
User input:
5-digit floating-point number
Factory setting
Depends on the nominal diameter, fluid and country (Page 122 ff.)
Transducer Block "Display" (Endress+Hauser parameters) / base index 700
Parameter Write access for
operating mode
(MODE_BLK)
Description