Proline Prowirl 72 FOUNDATION Fieldbus 11 Operation via FOUNDATION Fieldbus
Endress + Hauser 113
System -
Alarm Delay
AUTO - OOS Use this function to define a time span for which the criteria for an error
have to be satisfied without interruption before a fault or notice message is
generated.
! Note!
Depending on the setting and type of error, this alarm delay affects both the
display and the outputs of the FOUNDATION Fieldbus.
User input:
0 s to 100 s (in steps of one second)
Factory setting:
0 s
" Caution!
If this parameter is used, fault and notice messages are delayed by the time
corresponding to the setting before being forwarded to the downstream
function blocks or the fieldbus host system.
It is therefore imperative to check in advance whether a delay of this nature
could affect the safety requirements of the process. If fault and notice
messages may not be suppressed, a value of 0 seconds must be entered
here.
System -
Simulation
Failsafe Mode
AUTO - OOS Use this function to set the totalizers to their defined failsafe modes, in
order to check whether they respond correctly.
The failsafe mode of the totalizer is determined via the "Totalizer - Failsafe
All" parameter in the Transducer Block "Totalizer" (Page 106).
Device response when error simulation is active:
Device status notice message #691 "SIM. FAILSAFE" active,
(Page 53)
Options:
Off
On
Factory setting:
Off
System - Reset AUTO - OOS Use this function to reset the measuring system.
Options:
No
Restart System
Restart without disconnecting main power.
Reset Delivery
Restart without disconnecting main power, the saved settings of the
delivery status (factory settings) are applied.
Factory setting:
No