Function group
CURRENT OUTPUT
DUAL RANGE
MODE
For specific applications the scaling of a second end value is useful or
possibly required, e.g. for a higher resolution of the measuring signal with very
small flow velocities.
By activating the dual range mode, the system automatically changes between
full scale value 1 and 2 during normal measuring operation. Full scale value 1
and 2 are freely selectable.
Note!
The appropriate configuration enables the actual full scale value to be
supplied or signalled via both relays (see following Figure and page 61).
In this case the following applies:
Full scale value 1 active Relay 1 or 2 energised (live)
Full scale value 2 active Relay 1 or 2 de-energised (dead)
If the Promag 33 measuring electronics are fitted with a communication
module “RS 485”, then the full scale values 1/2 can also be activated using
the auxiliary input (see page 69).
6
OFF
–ON
Example (0...20 mA; Full scale 1 < Full scale 2)
bab
aba
a Relay energised
b Relay de-energised
ba009y37
F1 < F2
F1 > F2
smaller larger
full scale full scale
Note!
6 Description of Functions Promag 33
50 Endress+Hauser