11 Additional Functions
Additional Functions contains a number of functions which maybe required during the
Fieldgate life-cycle but not for everyday operation. The functions offered depend upon the
parametrization tool. In FieldCare the corresponding function is called by right-clicking on
the Fieldgate SWG70 node and selecting Additional Functions.
11.1 Reset
Reset allows the Fieldgate, the instrument list and the network to be reset, see table. The
reset is initiated by pressing the appropriate button. During reset, communication with the
network will be temporarily lost.
1. Click Additional Functions> Reset to open the dialog:
Reset options
Parameter group Meaning
Device Reset Press this button to restart Fieldgate without any impact on the established
network.
Fieldgate SWG70 is restarted with all user settings intact.
Rebuild Instrument List Press this button to regenerate the instrument list.
Create a backup of the existing instrument list before resetting. See
Chapter 10.1.
The existing instrument list is overwritten.
The Modbus addresses of the devices in the network may change.
Reform Network Press this button to restart and reestablish the network.
The existing instrument list is overwritten.
The Modbus addresses of the devices in the network may change.
Depending on the size of the network, this process may take some minutes.
Reset Diagnosis Bits Press this button to reset the diagnosis bits in Fieldgate SWG70.