Engineering WirelessHART Fieldgate SWG70
84 Endress + Hauser
HART commandos Enter the settings for the HART commands in the Variable Configuration area. The HART
command is activated only when the corresponding Active checkbox is ticked.
NOTICE!
• In order to minimize the scanning time, you must enter the same parameters for the
Sampling Rate and Request Data that you have already used for the WirelessHART
Adapter (SWA70).
For example, when a WirelessHART Adapter transmits Command 2 every 15 minutes and
Command 48 every 60 minutes, only CMD 2 and CMD 48 should be activated and the
corresponding times entered in the Sampling Rate field.
For more information see the WirelessHART Adapter operating instructions.
Menus
File menu
Edit menu This menu corresponds to the context menu which opens when an object is right clicked.
Parameter Meaning
Device Identification Identification of the device. Options: every minute or every hour.
CMD 1: Primary Value Transmits the primary variable and its unit at the selected interval.
CMD2 Loop Current and % of
Range
Transmits the value of the 4…20 mA signal and the corresponding percentage
value at the selected interval.
CMD 3: Dynamic Variables
and Loop Current
Transmits the value of the 4…20 mA signal and up to four predefined process
variables (PV, SV, TV and QV) and corresponding units at the selected interval.
CMD 9: Device Variables
with Status
Transmits the values, units and status of up to eight field device variables at the
selected interval.
CMD 33: Device Variables Transmits the values and units of up to four field device variables at the selected
interval.
CMD 48: Additional Device
Status
Transmits the entire device status information at the selected interval.
Designation Meaning
New Opens an empty configuration file.
Recent Opens the last used configuration file.
Open Opens a configuration file.
Open Active Opens the configuration file that is accessed by the WirelessHART OPC server.
Save As Saves a configuration file with a new file name and in any desired folder.
Save Active Saves the configuration file under the name "GatewayConfiguration.xml" in a
predefined folder. The WirelessHART OPC server accesses this file.
Exit Closes the "WirelessHART Fieldgate Configurator" program.
Designation Meaning
Add Add an object such as a Folder, Adapter or Subdevice (field device). The device tree
in the left pane is extended as appropriate.
– Folder: the object "Folder" can be used to structure the device tree. "Folder" may
contain several adapters and field devices (subdevices).
– Adapters: adapters such as a WirelessHART Adapter SWA70 or a field device
with antenna. You can add several field devices below an adapter.
– Subdevices: field devices without an antenna. You cannot add other objects
below a field device (subdevice).
Delete Delete an object.
Cut Delete an object and put it in the clipboard.
Copy Copy an object.
Paste Add an object from the clipboard.