WirelessHART Fieldgate SWG70 Fieldgate configuration
Endress + Hauser 51
Ethernet parameters
8.3.2 Serial (RS-485)
The parameters contained in this leaf pertain to the set up of the serial interface offered by
Fieldgate SWG70.
1. Click Wired Communication => Interfaces => Serial to display the associated
parameters:
2. Configure the serial interface for HART or Modbus RTU as required.
3. After configuration, set up the interface protocol parameters in the appropriate
"Protocol" leaf.
Modbus serial allows access for one master. See Chapter 8.4.4 "AMS via Ethernet" on
page 54.
HART serial allows access for one primary master and one secondary master. See
Chapter 8.4.3 "HART via Ethernet or RS-485" on page 53.
Parameter Meaning Default
IP Address
Assignment
(DHCP, DNS)
Specifies whether Fieldgate SWG70 IP network and DNS address is to be
assigned manually or automatically.
Manually: The settings in the dialog are used
Automatically: The IP address of the DNS is assigned by a DHCP server
Manually
IP Address Sets fixed fieldgate IP network address for manual assignment mode 192.168.1.1
Netmask Sets subnet mask IP network address for manual assignment mode 255.255.
255.0
Gateway Address Sets default gateway TCP/IP network address
This setting is currently not actively used by Fieldgate
0.0.0.0
DNS 1 Sets preferred DNS server IP address for manual assignment mode
This setting is currently not actively used by Fieldgate
0.0.0.0
DNS 2 Sets alternative DNS server IP address for manual assignment mode
This setting is currently not actively used by Fieldgate
0.0.0.0
MAC Address Displays the MAC address of the WirelessHART gateway.
Note that the MAC address is a characteristic of the device itself and
cannot be changed. Each device has its own MAC address.
Write Ethernet
Information
Downloads the changed parameters to the Fieldgate
If the IP address was changed, communication will be lost
If the other addresses were changed, communication will be interrupted
for a short period