WirelessHART Fieldgate SWG70 Commissioning
Endress + Hauser 37
7.3 Creating a FieldCare project
Creating a FieldCare project will allow you to configure Fieldgate SWG70 and any HART
device (field device or adapter) in the wireless network via its DTM. The configuration of a
field device can be taken from the manufacturer’s operating manual, the configuration of
the adapter is described in Operating Instructions BA00061S/04/en, SWA70 Wireless
Adapter.
7.3.1 Adding the HART IP CommDTM
The HART IP CommDTM is required for communication via Ethernet with FieldCare.
NOTICE!
If you wish to connect to FieldCare via the RS-485 interface, the HART Communication
CommDTM must be added and configured instead of the HART IP CommDTM.
The procedure is similar to that described here, whereby the configuration involves other
parameters such as selection of multiplexer option, COM port and baudrate.
1. In the FieldCare project workspace, right-click on the Host Computer node and select
Add Device:
2. The Add New Device dialog opens:
Select HART IP Communication and press OK.
The dialog closes and the HART IP Communication DTM is added below the Host
node.
3. If desired, the HART IP Communication DTM can be now configured offline.
Right-click on the node and select Configuration.
The node name and timeout (default 10000 ms) can be changed.
The changes are accepted when the Apply button is pressed.