Fieldgate configuration WirelessHART Fieldgate SWG70
54 Endress + Hauser
HART parameters
8.4.4 AMS via Ethernet
If you would like to integrate Fieldgate SWG70 into Emerson’s Asset Management System
(AMS), this must be done via an Ethernet port. In rare cases you will need to change the port
number. The default port setting is "33333".
1. Click Wired Communication => Protocols => AMS.
Parameter Meaning Default
Bus Address Selection Specifies whether hardware (DIP switch 0–3) or software bus address
settings are to be used
DIP switch: 0 –15
Software: 0 –63
Software
Bus Address Sets the HART address of the wireless fieldgate when Bus Address
Selection is set to Software
When DIP-Switch is selected, displays the setting
1
Baud Rate Selection Specifies whether hardware (DIP switch 4–5) or software baudrate
settings are to be used
DIP switch: 9600 Bit/s –57600 Bit/s
Software: 1200 Bit/s –115200 Bit/s
Software
Baud Rate Sets the baudrate of the wireless fieldgate when Baud Rate Selection is set
to Software
When DIP-Switch is selected, displays the setting
19200
Port Number Sets the Fieldgate SWG70 Ethernet port number for HART via UDP/TCP
transmission
If the port number is changed, the default port remains open
HART UDP allows access for two primary masters and two secondary
masters
HART TCP allows access for one primary masters and one secondary
master
5094