Commissioning WirelessHART Fieldgate SWG70
34 Endress + Hauser
7.1 Ethernet connection
The Ethernet connection of Fieldgate SWG70 allows communication with a computer via the
integral Web Server or via FieldCare.
The following requirements must be met:
Internet Protocol TCP/IP is installed on your computer and is active.
You have administration rights for your computer and network.
You have an set of IP addresses that have been authorized by your IT department.
Any proxy server for your Internet Browser is disabled.
Firewalls allow communication on port 80, 433, 502, 3333 and 5094.
Fieldgate SWG70 is delivered with the default IP address:
192.168.1.1
NOTICE!
By default, the IP address of the WirelessHART Fieldgate EtherNet/IP version is
automatically assigned via DHCP. Please contact your network administrator to identify
the automatic set IP address, if necessary.
Alternative 3
rd
party IP scanner software i.e. “BOOTP Utility Software” from Rockwell
Automation enables you to scan the Ethernet network and being able to assign a dedicated
IP address i.e. 192.168.1.1 to the WirelessHART Fieldgate. Please consider WirelessHART
Fieldgate MAC address is required to be able to set a dedicated IP address with “BOOTP
Utility Software” from Rockwell Automation.
Please find below path to Rockwell Automation “BOOTP Utility Software” download and
instruction page:
1. Go to http://www.rockwellautomation.com
2. Click “Products”
3. Click “Reliance Electric Drives”
4. Click “Software”