EasyManua.ls Logo

Endress+Hauser WirelessHART Fieldgate SWG70 - Modbus in Fieldgate

Endress+Hauser WirelessHART Fieldgate SWG70
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WirelessHART Fieldgate SWG70 Modbus Interface
Endress + Hauser 115
Modbus overview
16.1.2 Modbus in Fieldgate
Fieldgate SWG70 is equipped with both a Modbus serial and Ethernet interface. As a result,
it can be operated in one of the following roles:
Modbus Serial Slave
Modbus TCP Slave
A serial or TCP slave can be accessed by one Modbus master only.
Establishing
communication
As a TCP slave, Fieldgate SWG70 will normally communicate with the master via Port 502.
If this port is unavailable, it is possible to specify a secondary TCP/IP port number.
Modbus commands Fieldgate SWG70 support for Modbus functions is currently as follows:
Modbus RTU Modbus TCP
Standard compliance "Modbus over Serial Line" V1 "Modbus over TCP" V1
Physical layer RS-485 Ethernet
Transmission mode RTU (binary mode) TCP
Baudrates 1200 bit/s, 2400 bit/s, 4800 bit/s,
9600 bit/s, 19200 bit/s, 38400 bit/s,
57600 bit/s, 115200 bit/s
100 MBit/s
Parity Odd, Even, None
Stop bits 1; 1.5; 2
Polling address 1...247
Port No. 502
Capabilities Input registers starting at Modbus address 30013
HART Command 3 dynamic variables mapped into input registers
2 input registers map a single HART dynamic variable
32bit HART floating point format used
Status information mapped on dedicated input registers
Function Function Code Hex Function supported
Read discrete inputs 2 0x02 Yes
Read coils 1 0x01 No
Write single coil 5 0x05 No
Write multiple coils 15 0x0F No
Read input register 4 0x04 Yes
Read holding register 3 0x03 Yes
Write single register 6 0x06 No
Write multiple registers 16 0x10 No
Read/Write multiple register 23 0x17 No

Table of Contents

Other manuals for Endress+Hauser WirelessHART Fieldgate SWG70