Operation WirelessHART Fieldgate SWG70
32 Endress + Hauser
DIP switch positions
Security mode When DIP switch 8 is OFF, it is not possible to download the Network ID and the Join Key to
the Fieldgate. See Chapter 8.3.2 "Serial (RS-485)" on page 51. Fieldgate SWG70 is delivered
with the download enabled by default, i.e. DIP switch 8 is ON.
Switch Function 1 234Value 1234Value
1 – 4 HART device address
1)
OFF OFF OFF OFF 0 OFF OFF OFF ON 8
ON OFF OFF OFF 1 ON OFF OFF ON 9
OFF ON OFF OFF 2 OFF ON OFF ON 10
ON ON OFF OFF 3 ON ON OFF ON 11
OFF OFF ON OFF 4 OFF OFF ON ON 12
ON OFF ON OFF 5 ON OFF ON ON 13
OFF ON ON OFF 6 OFF ON ON ON 14
ON ON ON OFF 7 ON ON ON ON 15
5 6 Value 5 6 Value
5 and 6 Baud rate of RS-485
interface
OFF OFF 9600 bit/s OFF ON 38400 bit/s
ON OFF 19200 bit/s ON ON 57600 bit/s
7 RS-485 termination • OFF = disconnected • ON = connected
8 Download
Join Key/Network ID
• OFF = disabled • ON = enabled
1) You can set up HART device addresses from 0 to 63 by software.